X-VOLT ® RHZ1-OL(S), AL - 12/20 (24) kV - Eca

Application

X-VOLT® RHZ1-OL(S), AL with fire-retardant sheath is used for medium voltage installations or distribution networks both indoors and outdoors. For example, for supplying transformer stations, infrastructure, wind turbines, solar parks, factory facilities, data centers, and similar applications.

Construction

Conductor

Aluminium, cl. 2

Insulation

Cross-linked polyethylene type XLPE according to IEC 60502-2 and type DIX3 according to HD 620-1, natural color. 
Semiconducting layer around the isolation. Easy strippable. 

Screen

Screen of Cu threads and hygroscopic tape

Outer sheath

Halogen free polyolefine type DMZ1 acc. to 620-1 and type ST7 acc. to IEC 60502-2, red with two grey stripes.

Technical data

Working temperature

-15° C to +90° C

Rated voltage

12/20 (24) kV

Bend radius

15 x cable diameter

Technical comments

Short circuit temp.: max 250° C / 5 sec.

Eca

Approvals

EN 50575, IEC 60228, IEC 60502-2, HD 620-1, IEC 60332-1, IEC 60754-1/2, UNE 211605, AENOR, RoHS, CE
Abrasion resistant
Bending radius 15 x cable diameter
Can be buried
Can lay in tubes
Flame retardant acc. to IEC 60332-1
For industrial use
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -15° C
Outdoor use
Torsion resistant
UV-resistant
SKU EAN CPR Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
10301095.H25WSI 5704403211029 Eca 1x95/25 280 Drum 28,6 1015
10301150.H25WSI 5704403211036 Eca 1x150/25 368 Drum 31,6 1250
10301240.H35WSI 5704403211043 Eca 1x240/35 502 Drum 36,1 1705
10301400.H35WSI 5704403211807 Eca 1x400/35 673 Drum 41,9 2325
10301630.H50WSI 5704403212439 Eca 1x630/50 895 Drum 50,0 3355