Drum Cable - 0,6/1 kV

Application

DRUM CABLE is ideal for use in dry and humid areas, for various applications where high repetitive mechanical stresses occur.

Construction

Conductor

Stranded Cu, class 5

Insulation

XLPE

Conductor color

Power: Black, brown, grey, blue, yellow/green
Signal: White with black numbering

Filling sheath

Thermoplastic compound

Screen
Outer sheath

Halogenfree PUR, yellow

Technical data

Working temperature
Flexible: -30o C to +80o C
Fixed: -40o C to +80o C
Rated voltage

0.6/1 kV (1.2 kV)

Bend radius
Flexible: 10 x cable diameter
Fixed: 6 x cable diameter
Conductor temperature

+90o C

Technical comments

Off / rewind speed up to 150 m / min
Short-circuit temperature + 250 ° C
Tensile strength (nominal) 55 N / mm

Approvals

IEC 60502-1, CEI EN 60228, VDE 0293, VDE 0295, EN 50363, HD 308 S2
Abrasion resistant
Bending radius 10 x cable diameter
Environmentally friendly
Flexible
For industrial mobile use
For industrial use
For permanent outdoor installation
Halogen free
Impact resistance: medium
Low smoke emission during fire acc. to 61034
Max. working temp. +90° C
Min. working temperature -40° C
Oil and grease resistant
Oil resistant
Resistance towards oil and chemicals
Suitable for cable chains
Torsion resistant
UV-resistant
Water resistant
Withstands freezing
Withstands moisture
SKU EAN Dimension (mm) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
- - 3x120+3G25 - D./Cut 47,2 5341
- - 3x150+3G25 - D./Cut 53,1 6130
- - 3x150+3G25+2x2,5 - D./Cut 53,1 6146
- - 3x150+3G25+4x2,5 - D./Cut 54,3 6160
915004010 5704403036936 4G10 - D./Cut 19,6 633
915004016425 - 4G16+4x2,5 - D./Cut 24,3 1129
915004035 5704403055296 4G35 - D./Cut 30,1 1999
- - 4G35+2x(4x1,5C) - D./Cut 33,6 1502
915005010225 5704403084210 5G10+2x2,5 - D./Cut 22,4 980
915005016 5704403164233 5G16 - D./Cut 25,3 1173
915005025 5704403124633 5G25 - D./Cut 30,8 1703
9150360015 5704403194827 36G1,5 - D./Cut 25,4 992