NA2XS(F)2Y is used for installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.
Alu-threads, class 2
Extruded semi-conducting layer around the conductor
XLPE DIX8
Extruded semi-conducting layer around the insulation
Semi-conducting water blocking tape
Cu threads and Cu counter helix over tape material
Water blocking tape
Polyethylene DMP2, black
Laminated sheath
Polymer laminated aluminum tape 0.25 mm
PE-sheath
Cross and longitudinal watertightness
-20° C to +90° C
6/10 kV (12 kV)
21 kV
15 x cable diameter
SKU | EAN | Dimension (mm2) | Current Value (A) | Winding | Diameter (mm)* | Weight (kg/km)* | |
---|---|---|---|---|---|---|---|
871011463 | - | 1X50/16 | 183 | Drum | 25 | 850 | |
871011464 | - | 1X70/16 | 228 | Drum | 27 | 950 | |
871011465 | - | 1X95/16 | 278 | Drum | 28 | 1100 | |
871011466 | - | 1X120/16 | 321 | Drum | 30 | 1200 | |
871011467 | - | 1X150/25 | 364 | Drum | 31 | 1400 | |
871011468 | - | 1X185/25 | 418 | Drum | 33 | 1550 | |
871011469 | - | 1X240/25 | 494 | Drum | 35 | 1750 | |
871011470 | - | 1X300/25 | 568 | Drum | 37 | 2050 | |
871011471 | - | 1X400/35 | 660 | Drum | 40 | 2450 | |
871012925 | - | 1X400/50 | 660 | Drum | 40 | 2200 | |
871011472 | - | 1X500/35 | 767 | Drum | 44 | 2850 | |
871012053 | - | 1X630/35 | 890 | Drum | 49 | 2969 | |
871013230 | - | 1X800/35 | 1022 | Drum | 52 | 3400 | |
871013032 | - | 1X1000/35 | 1151 | Drum | 63 | 4780 | |