X-VOLT ® FR-N20XA8E-AR - 18/30 (36) kV

Application

X-VOLT® FR-N20XA8E-AR is used for medium voltage installations or distribution networks both indoors and outdoors.
Ex. for the supply of transformer stations, infrastructure, wind turbines, solar parks, factory plants, data centers along with others. 

Construction

Conductor

Aluminium, cl. 2

Insulation

Cross-linked polyethylene insulation, type PR, natural color. Cross-linked in catenary line with nitrogen atmosphere. 

Inner sheath

Insulation screen: Semi-conducting XLPE
Inner covering: Semi-conducting water-swellable tape
Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath

Screen

Strippable cross-linked semiconductor screen applied over insulation in a triple-extrusion process.
Aluminium foil. 

Outer sheath

Polyolefin, black

Technical data

Working temperature

-15 °C to +90 °C

Rated voltage

18/30 (36) kV (Uo/U (Um))

Bend radius

15 x cable diameter

Eca

Approvals

IEC 60754, NF C 33-226, EN 60228,
Bending radius 13 x cable diameter
Can be buried
Can lay in tubes
For use in cable trays
Halogen free
Max. working temp. +90° C
Outdoor use
UV-resistant
Water resistant
SKU EAN CPR Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
1040T050.FR - Eca 1x50 201 Drum - -
1040T095.FR 5704403205790 Eca 1x95 295 Drum 33,3 1080
1040T150.FR 5704403205806 Eca 1x150 377 Drum 34,7 1255
1040T240.FR 5704403205813 Eca 1x240 497 Drum 38,8 1650
1040T300.FR 5704403205837 Eca 1x300 550 Drum 40,7 1845
1040T400.FR 5704403205820 Eca 1x400 639 Drum 43,9 2225
1040T500.FR 5704403205844 Eca 1x500 709 Drum 47,9 2625
1040T630.FR 5704403205851 Eca 1x630 846 Drum 51,2 3140